Catalogue

Modular, four power levels

Fusion 2

Start with a few cabinets. If the need grows, add more.

One control cabinet drives one to eight battery cabinets. The system is sized by adding cabinets, without changing the architecture: from 261 kWh to 3.34 MWh with a single control cabinet.

Fusion 2 is a battery system without an inverter: the PCS is not integrated and is specified with the system. We size it and supply it with every project.

Add cabinets and the power follows: the interfaces are quick connectors, and extending a site already equipped does not mean redoing the installation. Cabinets stand side by side, which keeps the footprint small — and every cabinet added lowers the cost per installed megawatt-hour.

  • Solar plant — the primary target
  • Hydro plant
  • Grid services
  • Wind farm
  • Constrained footprint
Fusion control cabinet and three battery cabinets side by side

Configure

Add cabinets, read the power.

Control
836 kWh
418 kWh
1
418 kWh
2
Battery cabinets connected2

Reference

Manufacturer reference : YXYK-852314-E

Energy
836 kWh
Power
417.8 kW
Ratio
2 h

The ratio, in one line: power × duration = energy. A 2-hour system stores twice its power, a 4-hour system four times. For the same energy, a longer ratio needs less conversion power — and targets other revenue.

Datasheet (PDF)

Single-line diagram

How the current flows.

CABINET 1261 to 418 kWhbuilt-in HV boxCABINET 2261 to 418 kWhbuilt-in HV boxCABINET 3261 to 418 kWhbuilt-in HV box… up to 8 cabinets728 – 1,497 VCONTROL CABINETconversion · protection1,435 A · 1,672 kW max.EMS400 V ACSWITCHBOARDsiteGRIDdirect currentalternating current

Specifications

Technical specifications.

Battery cabinet — the four references

 Fusion 261Fusion 313Fusion 365Fusion 418
Configuration1P260S1P312S1P364S1P416S
Nominal energy261 kWh313 kWh365 kWh418 kWh
Power130.6 kW156.7 kW182.8 kW208.9 kW
Nominal voltage832 V998.4 V1,164.8 V1,331.2 V
Weight≤ 2.68 t≤ 3.0 t≤ 3.33 t≤ 3.65 t
ReferenceYXYK-552314-EYXYK-652314-EYXYK-752314-EYXYK-852314-E

Control cabinet

Conversion (PCS)
Not integrated — to be provided with the system, supplied by JR Batteries
Voltage range
728 – 1,497.6 V DC
Maximum current
1,435.43 A
Maximum power
1,671.98 kW
Auxiliary supply
400 V (IEC) · 480 V (UL), 50 / 60 Hz
Dimensions (W × D × H)
1,350 × 900 × 2,414 mm
Weight
≤ 0.75 t (European version)

Installation

Nominal current
157 A (maximum 179.4 A)
Battery cabinet dimensions
1,350 × 1,310 × 2,434 mm
Ingress protection
IP 54
Operating temperature
−30 to 55 °C
Cooling
Liquid
Fire suppression
Aerosol
Noise
< 79 dB at 1 m
Altitude
≤ 2,000 m (3,000 m as an option, at reduced power)

Standards and certifications

  • IEC 62619
  • IEC 60730-1
  • IEC 63056
  • IEC 62477-1
  • IEC 61000-6-2/4
  • IEC 62933
  • UN 38.3
  • UN 3480
  • UL 1973
  • UL 9540
  • UL 9540A
  • UL 60730-1
  • FCC part 15B

We size it with you.

The grid connection, the contract, the generation already in place: three facts are enough to know whether this range is the right one. If not, we point you to another.

See the other ranges