The VenturePro 250 brings together in a single cabinet the battery rack, the high-voltage box, the BMS, the auxiliary supply, liquid cooling, fire protection and the inverter (PCS). It connects directly at 400 V AC: no technical room to build, no inverter to source separately.
One rack, five modules of more than 52 kWh each, 314 Ah prismatic LFP cells. All assembled and tested in the factory.
- Industrial or commercial site with a low-voltage connection
- Shaving contracted-power peaks
- Storing the surplus of a rooftop solar plant
- Up to 12 cabinets in parallel on one 400 V bus

Configure
Add cabinets, read the power.
- Energy
- 500 kWh
- Power
- 250 kW
- Ratio
- 2 h
The ratio, in one line: power × duration = energy. A 2-hour system stores twice its power, a 4-hour system four times. For the same energy, a longer ratio needs less conversion power — and targets other revenue.
Single-line diagram
How the current flows.
Specifications
Technical specifications.
Battery
- Parallel operation
- Up to 12 cabinets on one 400 V AC bus
- Configuration
- 1P260S
- Nominal energy
- 250 kWh
- Nominal voltage
- 832 V DC
- Voltage range
- 728 – 936 V DC
- Cells
- 314 Ah prismatic LFP, 5 modules > 52 kWh
- Service life
- ≥ 8,000 cycles
Grid connection
- Nominal power
- 125 kW
- AC voltage
- 400 V (IEC version) · 480 V (UL version)
- Nominal current
- 180 A (400 V) · 150 A (480 V)
- Frequency
- 50 / 60 Hz
- Charge / discharge switchover
- < 20 ms
- Max. AC efficiency
- 90 % (auxiliaries excluded)
- Current distortion
- < 3 % at nominal load
Installation
- Dimensions (W × D × H)
- 1,350 × 1,400 × 2,250 (2,340) mm
- Weight
- ≤ 3,500 kg
- Ingress protection
- IP 54 (cabinet) · IP 65 (PCS) · IP 67 (pack)
- Operating temperature
- −30 to 55 °C, derated outside −15 / 45 °C
- Cooling
- Liquid
- Fire suppression
- Aerosol
- Noise
- ≤ 75 dB at 1 m
- Altitude
- ≤ 2,000 m
- Protocols
- CAN · Modbus TCP/RTU
- Warranty
- 5 years, 5- or 10-year extension available as an option
Standards and certifications
- IEC/EN 62477-1
- EN IEC 61000-6-2
- EN IEC 61000-6-4
- EN 50549-1
- IEC 62619
- IEC 60730-1
- UN 38.3
- UN 3480
- UL 1741
- UL 1973
- UL 9540
- UL 9540A
We size it with you.
The grid connection, the contract, the generation already in place: three facts are enough to know whether this range is the right one. If not, we point you to another.