Catalogue

All-in-one cabinet

Venture Pro

One cabinet, everything inside.

The VenturePro 250 brings together in a single cabinet the battery rack, the high-voltage box, the BMS, the auxiliary supply, liquid cooling, fire protection and the inverter (PCS). It connects directly at 400 V AC: no technical room to build, no inverter to source separately.

One rack, five modules of more than 52 kWh each, 314 Ah prismatic LFP cells. All assembled and tested in the factory.

  • Industrial or commercial site with a low-voltage connection
  • Shaving contracted-power peaks
  • Storing the surplus of a rooftop solar plant
  • Up to 12 cabinets in parallel on one 400 V bus
VenturePro 250 cabinet, closed, three-quarter view

Configure

Add cabinets, read the power.

250 kWh
1
250 kWh
2
Cabinets in parallel2
Energy
500 kWh
Power
250 kW
Ratio
2 h

The ratio, in one line: power × duration = energy. A 2-hour system stores twice its power, a 4-hour system four times. For the same energy, a longer ratio needs less conversion power — and targets other revenue.

Datasheet (PDF)

Single-line diagram

How the current flows.

VENTUREPRO 250 CABINETMODULE 1MODULE 2MODULE 3MODULE 4MODULE 55 × 52 kWh · LFP 314 Ah832 VHV BOXBMS · pre-chargePCS125 kW400 VSWITCHBOARDsiteGRIDdelivery pointdirect currentalternating current

Specifications

Technical specifications.

Battery

Parallel operation
Up to 12 cabinets on one 400 V AC bus
Configuration
1P260S
Nominal energy
250 kWh
Nominal voltage
832 V DC
Voltage range
728 – 936 V DC
Cells
314 Ah prismatic LFP, 5 modules > 52 kWh
Service life
≥ 8,000 cycles

Grid connection

Nominal power
125 kW
AC voltage
400 V (IEC version) · 480 V (UL version)
Nominal current
180 A (400 V) · 150 A (480 V)
Frequency
50 / 60 Hz
Charge / discharge switchover
< 20 ms
Max. AC efficiency
90 % (auxiliaries excluded)
Current distortion
< 3 % at nominal load

Installation

Dimensions (W × D × H)
1,350 × 1,400 × 2,250 (2,340) mm
Weight
≤ 3,500 kg
Ingress protection
IP 54 (cabinet) · IP 65 (PCS) · IP 67 (pack)
Operating temperature
−30 to 55 °C, derated outside −15 / 45 °C
Cooling
Liquid
Fire suppression
Aerosol
Noise
≤ 75 dB at 1 m
Altitude
≤ 2,000 m
Protocols
CAN · Modbus TCP/RTU
Warranty
5 years, 5- or 10-year extension available as an option

Standards and certifications

  • IEC/EN 62477-1
  • EN IEC 61000-6-2
  • EN IEC 61000-6-4
  • EN 50549-1
  • IEC 62619
  • IEC 60730-1
  • UN 38.3
  • UN 3480
  • UL 1741
  • UL 1973
  • UL 9540
  • UL 9540A

We size it with you.

The grid connection, the contract, the generation already in place: three facts are enough to know whether this range is the right one. If not, we point you to another.

See the other ranges