JR Batteries — BESS, Battery Energy Storage System
Catalogue

Solar plant and data centre

DC800

VentureEdge 800 cabinet available early 2027

Storage that grafts onto a plant, or backs up a data centre.

Two formats for the same building block. The VentureEdge 800 cabinet — 418 kWh and 209 kW, 800 V output, one to five cabinets in parallel — and the VentureBooster 800 container, which brings five of these racks together for 1 MW and a little over 2 MWh.

Both connect to the plant's 800 V bus, at the output of the solar inverters. They therefore need no transformer of their own: where a conventional installation lines up two — one for solar, one for the battery — only one remains.

The same conditions apply to a data centre: a supply to protect, an existing bus to graft onto, and a power level to hold without interruption. There the DC800 acts as reserve and peak shaving.

  • Existing solar plant to be equipped with storage
  • Data centre: backup and peak shaving on the existing bus
  • Site equipped in stages, one cabinet at a time
  • Shifting daytime export to the expensive hours
  • Limiting curtailment on a saturated grid connection
Armoire VentureEdge 800, refroidissement liquide, portes fermées

Configure

Add cabinets, read the power.

418 kWh
1
418 kWh
2
Cabinets in parallel2

Reference

Manufacturer reference : YXHK-209K/852314-X

Energy
836 kWh
Power
418 kW
Ratio
2 h

The ratio, in one line: power × duration = energy. A 2-hour system stores twice its power, a 4-hour system four times. For the same energy, a longer ratio needs less conversion power — and targets other revenue.

Datasheet (PDF)

Single-line diagram

One transformer instead of two.

WITH VENTUREBOOSTER 800PV ARRAYmodulesPV INVERTERVENTUREBOOSTER1 MW / 2.09 MWh800 V AC BUSTRANSFORMERsingleGRIDHV GRIDCONVENTIONAL SET-UPPV ARRAYPV INVERTERTRANSFORMER 1BATTERYBESS INVERTERTRANSFORMER 2GRIDHV GRIDdeux transformateurs, deux jeux de protections

Specifications

Technical specifications.

VentureEdge 800 cabinet

Nominal energy
418 kWh
Nominal power
209 kW
Voltage
800 V AC
Nominal current
150.8 A AC side · 157 A DC side (maximum 179.4 A)
Voltage range
1,164.8 – 1,497.6 V DC
Charge / discharge rate
0.5 P
Overload
110% continuous
Power factor
0.99 / −1 to 1
Peak efficiency
90% (excluding auxiliaries)
Paralleling
Up to 5 cabinets, AC side
Auxiliary consumption
3.2 kW
Dimensions (L × W × H)
1,600 × 1,350 × 2,450 mm
Ingress protection
IP 54
Altitude
≤ 2,000 m (3,000 m with derating)
Operating temperature
−30 to 55 °C
Cooling
Liquid for the batteries, air for the PCS
Fire suppression
Electrically triggered aerosol
Noise
≤ 75 dB at 1 m
Availability
Early 2027

Container — DC side

Nominal energy
5 × 418 kWh, i.e. 2,090 kWh
Configuration
5 racks of 416 cells in series
Cells
LFP 3,2 V / 314 Ah
Nominal current
157 A (maximum 179.4 A)
Voltage range
1,164.8 – 1,497.6 V DC
Charge / discharge rate
0.5 P

Container — AC side

Nominal power
5 × 200 kW, i.e. 1 MW
Voltage
800 V AC (−12% / +10%)
Connection
3 conductors + earth
Nominal current
5 × 145 A
Frequency
50 / 60 Hz
Power factor
0.99 / −1 to 1
Harmonic distortion
< 3% at rated load
Peak efficiency
88% (excluding auxiliaries)

Container — installation

Dimensions (L × W × H)
6,058 × 2,438 × 2,896 mm
Weight
≈ 25 t
Ingress protection
IP 55
Auxiliary consumption
22 kW
Operating temperature
−30 to 55 °C
Cooling
Liquid for the batteries, air for the PCS
Fire suppression
Electrically triggered aerosol
Noise
≤ 75 dB at 1 m
Communication
RS-485 · Ethernet · CAN, Modbus TCP/RTU

Standards and certifications

  • IEC 62619
  • IEC 60730-1
  • IEC 63056
  • IEC 62477-1
  • IEC 61000-6-2/4
  • UE 2023/1542
  • UN 38.3
  • UN 3536

We size it with you.

The grid connection, the contract, the generation already in place: three facts are enough to know whether this range is the right one. If not, we point you to another.